XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
5.2
Configure Group of Devices
This option allows a group of devices to be
deleted or all set to the same type. The devices
must be at consecutive addresses on the same
loop and in the same zone, and if being deleted
they must be of the same type.
This example shows the procedure for
sensors. The procedure for modules is
identical. You cannot mix sensors and modules
in this procedure.
To start this option:
1
From the Loop Device Configuration menu,
select the Configure Group of Devices
option.
2
Select the loop in which the devices are
fitted.
3
Select either sensor or module.
4
Select the address range by entering the
first address and then the last address. In
this example, 10 is entered as the first
address, it therefore becomes the lowest
address in the range that can be entered
for the last address.
Note:
GAS sensors require at least three
consecutive sensor addresses. If the
selected range has an IIG-1 or IIG-4
device at one of the next two addresses
below the range the message ‘This
address is not available: GAS sensor
occupying one of the previous two
addresses.’ is displayed. It is not
possible to configure a group of GAS
sensors using the Configure Group of
Devices option.
NUMERIC KEYS,
THEN
MAKE
SELECTION
NUMERIC KEYS,
THEN
SEE NEXT PAGE
NUMERIC KEYS,
THEN