INPUT NON-FIRE ACTIVATION, IF ANY OF THE
‘OTHER ACTIONS’ OUTPUT OPTIONS 1 TO 8 ARE
CHOSEN.
7.6.2.6 Other Output Options
For the MUTE INTERNAL BUZZER, SILENCE
SOUNDERS, SYSTEM RESET, TRANSFER
FLAG, System in NIGHT mode, System in DAY
mode, Extend Investigation Delay and OVER-
RIDE Investig. Delay options there are no zone
or cell selections. The Time-of-Day option is
provided.
Further information about the use of
TRANSFER FLAGs is given in
Section 7.9
.
Note:
Actions occur when input switch goes
from open to closed, thus to toggle
between Day and Night modes two
momentary action input switches are
required. An alternative method of
achieving this using one switch is
described in
Section 11.19
step 3.
7.6.2.7 Set to Thermal-Only mode
This menu option is only available if the input
is NON-FIRE ACTIVATION or TRUE. The only
selections are zone or range of zones (not
cell[s]) and Time-of-Day. While the input is
active, all Multi-criteria sensors so configured
(
Sections 5.1.3
and
5.3.2
) and present in the
selected zone(s) are set to their L6 Thermal-
Only mode.
7.6.3 Completion of New Entry
Press
to confirm the new entry.
Note:
At this stage, time-of-day options cannot
be reviewed and the delay # number is
not determined and is shown provisionally
as ‘1’.
If you exceed the maximum number of entries
allowed in the Control Matrix (see
Section 7.1
)
the message ‘ERROR: MEMORY FULL’ is
displayed.
If, after an existing Control Matrix entry is
amended, it is identical to the one it replaces,
there is no confirmation prompt and the top
line displays ‘Control Matrix Entry Unchanged’.
CONTROL MATRIX
ENTRY TAKES EFFECT