35
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
5.1.2.5 Edit Verification Delay
Set the verification delay within the displayed
range. RANGE! is displayed if the entered
number is out of range. Refer to
Section 13
for recommended verification delays.
Alarm verification display is shown on the left.
The Fault verification display has the same
layout.
5.1.2.6 Edit Priority Option
Set the priority polling ON of OFF. When ON
the device will scan at intervals of less than
one second.
A maximum of 43 devices per loop may be
designated as priority; however, to obtain the
1-second scan interval do not designate more
than 21 devices per loop as priority (as more
devices are assigned priority scan status, the
scan rate becomes slower for the remaining
devices).
5.1.2.7 Time of Day
The sensitivity can be varied at different times
of day.
Refer to
Section 9
for details of time-of-day
programming.
Note:
If the device’s alarm sensitivity is
changed, the time of day variation is
cancelled automatically to prevent it
going out of range.
NUMERIC
KEYS, THEN