Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
b. After a timeout. Numeric entry up to 1440
minutes (24 hours) followed by
, then
confirm.
c. At set times of day. Edit this in the same
manner as other time-of-day programs (see
Section 9
) - in this case there are only two
time fields for each day-of-week set, not a
pair of start and end times. Also, there is
no ‘level’ adjustment and no ‘Manual
Override’. Confirm the changes.
2
Set the required buzzer time interval during
disablement, and confirm.
3
Set the SOUNDER DISABLEMENT
Access level, then confirm. To comply with
EN54-2, level 2 should be selected.
4
Select which disablements can be
controlled by a remote panel or switch, then
confirm.
5
Set the required disablement indication.
IF CANCEL
AFTER TIMEOUT
(AT CONFIRM
PROMPT)
IF CANCEL AT SET
TIME(S) OF DAY
FROM PREVIOUS PAGE
NUMERIC
ENTRY, THEN
EN54-2: 9.1.2
SOUNDER
DISABLEMENT must
be at Access level 2
(AT CONFIRM
PROMPT)
DISABLEMENT SETTINGS
TAKE EFFECT
MAKE SELECTION
(AT CONFIRM
PROMPT)
(AT CONFIRM
PROMPT)
EN54-2: 9.2
Delays are a
disablement and
require the general
disablement
indicator