XLS80e Fire Alarm Control Panels
11.6 Automatic Test Options
This setting allows the user to specify the day-
of-week and time-of-day at which analogue
sensor automatic tests occur:
1
Set the day field to one of:
a. NONE. Automatic tests do not occur. The
time field is not shown.
b. DAILY. The Test menu displays DAILY.
c. A specific day of the week. The Test menu
displays WEEKLY.
2
Set the time field, digit by digit, to the time
of day at which the test is to occur. Use the
and
pushbuttons, not the numeric
pushbuttons.
Note
: There is no unattended test facility for
modules (including MCPs). These
devices can only be tested manually,
hence in the majority of installations the
Walk Test is still a routine requirement.
No report is generated by the panel unless a
sensor fails the test. In the unlikely event that
a sensor remains in an Alarm state (possibly
due to a real fire) following the cessation of
the test, for safety reasons this has to be
handled as an Alarm of Fire. Users are therefore
recommended to select a day and time when
authorised persons are likely to be present and
can deal with both a fault report from the panel
and the remote risk of a false alarm.
11.7 Disablement Options
This setting determines:
a. The circumstances under which
disablements are cancelled.
b. The intermittent buzzer interval for
disablement.
c. The access level required to disable the
sounders.
d. What can be disabled from a remote panel
or switch.
e. Whether the common DISABLEMENT LED
illuminates when the DELAYS ACTIVE LED
is lit.
1
Select one of the options for cancellation
of disablements:
a. Manual cancellation only.
TEST SETTINGS TAKE EFFECT
(AT CONFIRM
PROMPT)
MAKE SELECTIONS
EN54-2: 9.1.2
Disablement and re-
enablement MUST be a
manual operation.
TO NEXT PAGE