Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
IF OPTION 6 (OTHER EVENTS) IS CHOSEN, SUB-
MENU IS DISPLAYED:
IF OPTION 6 (EXTINGUISHING SYSTEM) IS
CHOSEN:
SELECT THE OUTPUT DEVICE
7.6.1.7 OTHER EVENTS
The EVACUATE Pushbutton, RESET
Pushbutton, SILENCE SOUNDERS Pushbutton,
Manual Call Point in WALK TEST and TRUE
input options do not require any further definition
(except that EVACUATE can be from ‘Any’ panel
or from a specified panel); when they are
selected the next display is the OUTPUT options.
EN54-2: 9.1.2
Use of TRUE to
disable is not
allowed.
The TRANSFER FLAG input requires a flag
number to be specified, i.e. the same number
as the corresponding Control Matrix output
action.
CAUTION:
This product is not compliant
with EN 12094-1.
EN
12094-1
!
EN
12094-1
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
7.6.1.6 EXTINGUISHING SYSTEM
The Extinguishing System input requires a
system number to be specified, i.e. the same
number as the corresponding Control Matrix
output action. Up to 32 Systems can exist on
the panel. See
Section 7.8 Extinguishing
System Function
for further information.
Select whether the output action is to occur
before or after the delay configured in the
Control Matrix output statement. BEFORE
DELAY does not override the delay; it allows
an output to be activated before the timer
expires (e.g. use for warning lamps, sounders,
and the directional valve). Use AFTER DELAY
for the releasing valve.
The only output for this input category is
‘Specified Individual Module’.