109
XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
12.1.1 CMX Modules
1
Select Individual device.
2
Select CMX modules.
3
Select the zone to which the module is
allocated to view a list of modules in the
zone (or ALL Zones to view details of all
modules).
4
A list of modules is displayed. Select the
required module.
Either move the highlight
to the required device or use the numeric
keys to enter the loop number and then the
device number (the device nearest in
number to that entered is then highlighted).
Note:
While a device is highlighted, press
to display its type, zone and value
(continuously updated). Press
to re-
display the device description.
5
The selected circuit operates.
6
The selected circuit stops operating.
Control Output/Sounder Test
1:
2:All Sounders on selected Loop
Service Tue 27-Jul-2004 11:20:07
Individual device
FROM PREVIOUS PAGE
Control Output/Sounder Test
1:
2:Sounder Circuit 1
3:Sounder Circuit 2
4:Sounder Circuit 3
Service Tue 27-Jul-2004 11:20:07
CMX Module