A3 - 3
Honeywell, Issue 9
March 2007
XLS80e Fire Alarm Control Panels
1.2.1 Location Text
To enter a panel location description, use the
pushbutton to move the cursor to the
‘Location’ column. Press the
pushbutton
to display the text editing screen. Enter the
desired text for the panel (up to 32 characters
- including spaces - are permissable).
Note:
How to use the text editor is described
in
Section 6
of this manual.
Press the
pushbutton to save the text entry.
The tabular-form screen is re-displayed with
the entered text highlighted now in the
‘Location’ column.
Once all data for that node has been entered,
this operation will have to be repeated at ALL
other stations on the network.
1.2.2 RS485 Repeaters
Note:
This procedure is described assuming
that you are familiar with using the panel
control keys to navigate the menus and
how to make appropriate option
selections. If in doubt, refer to
Section 1.2
of this Appendix.
This option allows the configuration of
repeaters on networked panels using the
RS485 communications link. Refer to the
XLS80e Series Installation & Comissioning
Manual (ref. 997-473) for details on fitting the
RS485 PCB in the control panel.
To configure repeaters at a panel, proceed as
follows:
At the appropriate panel, from the Access
level 3 menu (Service) select the Configuration
option (item 6). From the CONFIGURATION
menu select option 5, Network Configuration
to display the ‘NETWORK Configuration’ menu
as shown:
Select option 4, Repeaters only Configuration.
Enter the number of repeaters and confirm
using the
pushbutton.