XLS80e Fire Alarm Control Panels
Honeywell, Issue 9
March 2007
5.1.2.8 LED Blink Options
Select whether the device’s LEDs follow the
panel setting (
Section 11.2
) or are set to blink
or not (non-blink).
5.1.2.9 LED Also Controls
Select the required option:
a. NONE. There are no additional controls.
b. SOUNDER. For use with B601BH base
with integral sounder; the sounder will be
silenced by operation of the panel’s
SILENCE/RESOUND (to silence) or
RESET pushbuttons.
c. Non-Sil. Control. Used when auxiliary
equipment is driven in parallel with the
sensor LED. Control of this auxiliary
equipment is then independent of the
SILENCE/RESOUND pushbutton - it is only
switched off by operating the RESET
pushbutton.
5.1.2.10
End the Editing Session
When all the changes have been made, press
to confirm them. The panel then uses the
changed parameters.
THEN
Device Configuration - Loop n Sensor nn
Type OPT Zone nn Cell n
Zone <(no zone text defined) >
Loc. <Device text description >
LED BLINK MODE
=select *=edit =next device =finish
Follow Panel Setting
Device Configuration - Loop n Sensor nn
LED BLINK MODE
1:
2:Always BLINK
3:Always NON-BLINK
Follow Panel Setting
Device Configuration - Loop 1 Sensor 1
Type OPT Zone 20 Cell 0
Zone <Corridor >
Loc. <Ceiling >
LED also controls:
=select *=edit =next device =finish
NONE
Device Configuration - Loop 1 Sensor 1
LED also controls:
1:
2:SOUNDER
3:Non-Sil.CONTROL
NONE