5 UCN Exerciser
5.6 Analyzing Results
R688
HPM High-Performance Process Manager Service
399
December 2020
Honeywell
5.6 Analyzing Results
Connect Test Detail display
To see the results, chose the node of interest and select the
RESLTS DETAIL
(RESULTS DETAIL)
target on the Connect Test Summary display. This invokes the Connection Test Detail display as shown
in the following figure.
Figure 198 Connection Test Detail Display
Number of attempt errors
Check the boxes in the grid target for nodes 0, 5, and 7. The number in the lower right corner of the box
reports the number of attempts if the
ATTMPS
(ATTEMPTS) target is backlighted, or the number of
errors if the
ERRORS
target is backlighted on the Connect Test Summary display. The display is
selected with the
CONNECT TST SUM
(Connect Test Summary) target.
Problem correction
The node that has the highest number of errors is likely to be the node causing a problem. The problem
should be corrected by replacing the HPM UCN Interface
module or by checking the UCN cable
connections. If this does not correct the problem, call the Technical Assistance Center (TAC) for
assistance.