4 Fault Isolation
4.13 Power System Indicators
R688
HPM High-Performance Process Manager Service
383
December 2020
Honeywell
DC Out indicator
If a
DC Out
LED is off, ac line power has been lost (check the
AC In
LED) or the Power Supply
Module has failed. If the Power System is nonredundant, or if both
DC Out
LEDs are off, the HPM has
lost 24 Vdc. The CMOS backup system maintains power to the CMOS memory, so subsystem programs
are not lost. See the
Battery
LED description below. A set of annunciator contacts, which are illustrated
in Figure 187, open when these conditions occur.
Battery indicator
If the
Battery
LED is off and the
Charge
LED is on, the
48 Volt Battery
switch is in the off position
or the 48 V Battery Backup system has failed. A set of annunciator contacts, which are illustrated in
Figure 187, open when these conditions occur. If the Power System does not have the battery pack
option, the
Battery
LED will normally be on, and the
Charge
LED will normally be on.
Fan/Temp indicator
If the
Fan/Temp
LED is off, the fan in the Power Supply Module has failed or the temperature of the
HPM has exceeded a safe value. An annunciator contact, discussed below, is activated by any of the five
conditions described below.
AC In indicator
If the
AC In
LED is off, ac power to the HPM has been lost or the switch on the Power Supply Module
is off. Backup systems, if operating, are maintaining the unit. Check the
DC Out
and
Battery
indicators
to determine the state of the system. Some installations may have the Power Supply Modules connected
to the separate ac power sources to minimize outage caused by a power loss. Annunciator contacts,
illustrated in Figure 187, signifying power loss from either supply, are activated independently.
Charging indicator
When the
Charging
LED is off, the charging circuit that maintains the optional 48 V Battery Backup
system has failed. Check the batteries, their corresponding connections, and the charging circuits in the
Power Supply Module (s). An annunciator contact output, illustrated in Figure 187, is activated by this
condition.
Summary of Contents for HPM
Page 178: ......
Page 300: ......
Page 390: ......
Page 497: ......
Page 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...