3 UCN Status Displays
3.6 NIM Detail Status Displays
230
HPM High-Performance Process Manager Service
R688
Honeywell
December 2020
NIM Local UCN Statistics display-page 2
Figure 119 NIM Local UCN Statistics Display
– Page 2
Two pages
The
STATISTICS PAGE TWO
target on the first page display is used to request the second page of
statistics. The first page is chosen by selecting the
STATISTICS PAGE ONE
target on the second page
display. The
RESET LOCL STATISTICS
target on either page is used to reset the values of all the
statistics to zero for diagnostic purposes, not just those on the page being displayed.
Cable noise/silence
Not shown in the figures is a group of four messages pertaining to the detection of noise/silence on the
UCN cables. These messages, which appear immediately above the
LOCAL UCN STATISTICS -
PAGE 1
or
PAGE 2
heading, can be any combination of the following texts:
CABLE A NOISE
CABLE B NOISE
CABLE A SILENCE
CABLE B SILENCE
Time Sync operation
Normal Time Synch operation is for the Synchronizer NIM, the lowest-address NIM that has an EPNI
board and the best LCN clock status, to send hardware recognized Time Synch message, followed by a
matching synchtime message containing the exact time of the Time Synch message transmission. This is
done at nominal 6 second intervals.