HPM High-Performance Process Manager Service
R688
Honeywell
December 2020
IOP Slot Soft failure error codes
The following table defines the Input/Output Processor (IOP) Slot Soft failures. The recommended
corrective actions are included in the table.
Table 63 IOP Slot Soft Failure Error Codes
Error Code
Failure
Mnemonic
Description
Corrective Action
00
Null
No error
01
to
06
Not used.
N/A
07
EECKSMER
LLAI EEPROM checksum
during write.
Replace the FTA plug-in module or recalibrate.
08
EECNTERR
LLAI EEPROM counter error.
Replace the FTA plug-in module or recalibrate.
09
to
20
Not used.
N/A
21
INPTFAIL
Input failure.
Replace the IOP or check the FTA wiring.
22
Not used.
N/A
23
OUTPUTFL
Output failure (AO or DO).
Check the output connection at the FTA. If it is
good, try replacing the FTA and/or the
appropriate IOP card.
24
to
25
Not used.
N/A
26
DIAGCTFL
1
Input/output loopback failure for
the slot.
Replace the IOP when convenient. Use a
Standby Manual device if appropriate.
27
to
28
Not used.
Replace the IOP card. If the replacement card
provides the same results, call TAC for
assistance.
29
BADPLUGM
Plug-in module failure.
Test that the slot is wired correctly. If it is,
replace the FTA plug-in module.
30
Not used.
N/A
31
FTAMSMCH
FTA mismatched with slot
configuration.
Reconfigure or replace the FTA.
32
to
34
Not used.
N/A
35
BADADPJP
Illegal internal zero
configuration attempted on this
channel.
Check for an open thermocouple, fuse, or
replace the IOP.
1
Slot Soft failure only. The display is incorrect.