2 Equipment Description
2.15 Power Systems
90
HPM High-Performance Process Manager Service
R688
Honeywell
December 2020
CMOS backup time duration
The following CMOS backup durations are defined for a HPM cabinet containing redundant HPMMs
and a total of 40 IOPs (40 nonredundant or 20 redundant pairs). The time duration depends on which
type of power system exists in the specific HPM cabinet.
Early production Standard Power System versions = 12 hours
(uses three AA size NiCad batteries). This version of power system also exists in the currently
installed PM/APM cabinets.
Enhanced HPM Standard Power System = 45 hours
(uses three C size NiCad batteries)
Nearly all of the CMOS backup power is consumed by the HPMMs. A cabinet with a nonredundant
HPMM will have a battery backup time of approximately double the values listed above.
Adding/deleting IOPs does not affect the times to any great extent. The current draw of each IOP is
almost negligible.
Honeywell does not specify that upgrading an existent PM/APM cabinet to HPM functionality must
include a new power system. The user must decide if the current power system in their upgrade
PM/APM cabinet provides sufficient CMOS backup time. The newer enhanced Standard Power System
provides a longer CMOS backup time.
PSM redundancy requirements
Configuration rules specify that an HPM cabinet containing redundant HPMMs must have a power
system with redundant Power Supply Modules.