2 Equipment Description
2.24 IOP to FTA Cabling
R688
HPM High-Performance Process Manager Service
135
December 2020
Honeywell
2.24 IOP to FTA Cabling
Introduction
Each IOP has a cable that connects it to its associated FTA.
Standard FTAs
The cables for standard FTAs leave the FTAs at the top or center, travel up or down the right side of the
vertical FTA Mounting Channel, go over or under the center divider, and then connect to the associated
IOP card file connector on the 7-Slot or 15-Slot card file backpanel.
Galvanically Isolated FTAs
When mounted on a horizontal FTA Mounting Channel, the cables for Galvanically Isolated FTAs leave
the top side of the FTAs, travel up or down the left side of the horizontal FTA Mounting Channel, go
over or under the center divider, and then connect to the associated IOP connector on the 7-Slot or 15-
Slot card file backpanel.
Galvanically Isolated FTAs can also be mounted on vertical FTA Mounting Channels. When they are,
the reverse of the cabling rules that apply for the standard FTAs apply for Galvanically Isolated FTAs
because the vertical orientation of the FTA Mounting Channel is reversed.
External cabinet installation
The FTAs can also be installed on a panel that is external to the cabinet, up to 50 meters (164 feet) cable
length from the IOP. Shielded FTA cables must be used whenever the FTA is located outside of the
HPMM cabinet complex. See the
High-Performance Process Manager Installation
manual for additional
information.