3 UCN Status Displays
3.3 Detail Status Display Selection Procedures
R688
HPM High-Performance Process Manager Service
189
December 2020
Honeywell
IOP Detail Status Display procedure
Use the following procedure to select an IOP Detail Status display.
Step
Action
1
Depress the
<SYST STAT>
(System Status) key on the console to invoke the System
Status display. The System Status display is shown in Figure 88.
2
Choose the NIM node on the display grid and then select the
NTWK/HWY
target on the
System Status display for the network you wish to examine to invoke the UCN Status
display. The UCN Status display is shown in Figure 89.
3
Choose the HPM that is associated with the IOP of interest on the display grid and then
select the
DETAIL
STATUS
target on the UCN Status display to invoke the HPM
Status display. The HPM Status display is shown in Figure 92.
4
Choose the IOP of interest on the display grid and then select the
DETAIL STATUS
target on the HPM Status display to invoke the IOP Detail Status display. An example
of an IOP Detail Status display is shown in Figure 96.
IOP Detail Status display
Figure 96 IOP Detail Status Display