3 UCN Status Displays
3.4 Display Operation
192
HPM High-Performance Process Manager Service
R688
Honeywell
December 2020
Auxillary status
With TPN R684, when the EHPM
or
ENIM is configured and loaded, the text
EHPM
or
ENIM
is
displayed respectively in the Auxiliary Status area on the UCN Status Display.
This Auxiliary Status area of the UCN node shows any one of the following:
Control State status – when the
Control States
target is selected.
Auto Checkpoint state – when the
Auto Checkpt
target is selected.
UCN Cable status – when the
UCN Cable Status
target is selected.
EUCN Node Type – when no target is selected or when the
Load/Save Restore
or
Run States
target is selected.Status box target
The status box is also a target. A command target selected at the bottom of the display will execute the
command, if applicable, for the status box chosen.
Selecting the status box target
When chosen, the status box is backlighted blue and the primary HPMM address is highlighted in white.
Choosing the same status box a second time, before selecting a command target, highlights the secondary
HPMM address. A status box selection toggles between the primary HPMM address and the secondary
HPMM address each time it is chosen. Selecting a command target will execute a command against the
primary or secondary HPMM, whichever has been chosen.
Primary HPMM status
The possible status of the primary HPMM is defined in the following table with the color of the text
indicated.
Table 24 UCN Status Display
– Primary HPMM Status
Term
Definition
OK
(Text color
– blue)
Processing is in progress.
ALIVE
(Text color
– yellow)
Power is present, but no database or personality
program is loaded.
IDLE
(Text color
– yellow)
The database and personality program are loaded,
but no processing is in progress.
IOIDLE
(Text color
– yellow)
One or more IOPs are in the Idle state.
LOADING
(Text color
– yellow)
The HPM is being loaded with its personality program
and database.
NOTCONFG
(Text color
– yellow)
There is no UCN node configured for the HP
M’s UCN
node address.
POWERON
(Text color
– yellow)
The HPM is responding to the UCN but has not
performed its self-tests. This is a transitory state that
occurs when the HPMM is first powered on.
CONFGMIS
(Text color
– red)
The configured node type for the HP
M’s UCN node
does not match the actual node type.
FAIL
(Text color
– red)
The HPM has a Hard failure and access to IOP
status and data is unavailable. HPM control functions
have ceased. Effectively, this is a total failure.