7 IOP Calibration Procedures
7.5 Nonredundant HLAI IOP Calibration Procedure
R688
HPM High-Performance Process Manager Service
447
December 2020
Honeywell
Figure 216 Nonredundant HLAI Calibration Connections
User Inpu t Device
Volta ge Inp ut:
Cu rrent Inp ut:
0-5 volt
1-5 volt
4-20 mA
10-5 0 mA
5 V
5 V
VCAL Vo ltage Source
H
R3
ANALOG IN PUT H IGH LEVEL /SF1 IN PUT MU - TAIHO2
TER MINATION ASSY. N O. 513 04453 - 1 00 R EV
B
CAL
S1
1 (+)
2 (-)
TB1
TB2
TB3
VCAL
J1
DATE C OD E
+24 V
R1
R2
+
-
Volta ge
Source
5 V
5 V
T
B
4
Step
Action
4
Short the two calibration pads at the upper-left corner of the HLAI FTA as shown in
Figure 215 to start the calibration. For the Galvanically Isolated FTAs, two pins in the
Marshalling Panel connector are shorted together.
5
Ensure that the calibration target on the HLAI Detail Status display has changed back
to
ENABLE CALIBRATION
, indicating that the zero and span calibration process has
completed. Check for the Soft failure
CALIB ABORT
, which indicates bad calibration.
6
Disconnect the calibration voltage source wiring.
7
Inform the operator that the HLAI can be returned to on-line operation.