4 Fault Isolation
4.3 Fault Isolation Concepts
R688
HPM High-Performance Process Manager Service
327
December 2020
Honeywell
Table 58 Communications and Control Processor Hard Failure Codes
Error
Code
CPU
Failure Mnemonic
Description
Corrective Action
(See Table 57)
060F
Comm
CRASH
Trouble waiting on MTOS Event Flag
1.
2, 1
0610
Comm
CRASH
Trouble resetting MTOS Event Flag 1.
2, 1
0611
Comm
CRASH
Trouble resetting MTOS Event Flag 2.
2, 1
0612
Comm
CRASH
Trouble waiting on MTOS Event Flag
2.
2, 1
0613
Comm
CRASH
Trouble resetting MTOS Event Flag 3.
2, 1
0614
Comm
CRASH
Trouble resetting MTOS Event Flag 4.
2, 1
0615
Comm
CRASH
Size of a write request buffer is > 504
words.
2, 1
0616
to
067F
Comm
CRASH
Reserved for future HPI Subsystem
crash codes.
1
0680
Comm
CRASH
Memory allocated for EVT and HPI DB
is too small.
1
0681
Comm
CRASH
Structured constant security check fail
1.
2, 1
0682
Comm
CRASH
Structured constant security check fail
2.
2, 1
0683
Comm
CRASH
Structured constant security check fail
3.
2, 1
0684
Comm
CRASH
Structured constant security check fail
4.
2, 1
0685
Comm
CRASH
Structured constant security check fail
5.
2, 1
0686
Comm
CRASH
Structured constant security check fail
6
2, 1
0687
Comm
CRASH
Buffer Allocated for Data Base
handling is too small.
1
0688
Comm
CRASH
Control, I/O Link, or Remote processor
timeout.
2, 6, 7, 1
0689
Comm
CRASH
Change Task Priority fail 1.
2, 1
068A
Comm
CRASH
Change Task Priority fail 2.
2, 1
068B
Comm
CRASH
Change Task Priority fail 3.
2, 1
068C
Comm
CRASH
General Data record size has
changed.
1
068D
Comm
CRASH
Set/Reset Swap event flag failed.
2, 1
068E
Comm
CRASH
Wait for Swap event flag failed.
2, 1
Summary of Contents for HPM
Page 178: ......
Page 300: ......
Page 390: ......
Page 497: ......
Page 498: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...