3 UCN Status Displays
3.5 HPM Status Displays
218
HPM High-Performance Process Manager Service
R688
Honeywell
December 2020
LOAD/SAVE RESTORE display targets
The command targets at the bottom of the display in Figure 110 perform the functions defined in the
following table.
Table 38 HPM Status Display
– LOAD/SAVE RESTORE Target Selected
Target
Function
PROGRAM LOAD
Loads the on-process (regular) personality program and the
selected database to the chosen HPMM. If the primary
HPMM is chosen, the database is also restored in all IOPs
that are in the Idle state. The command is executed by
selecting the ENTER target.
RESTORE MODULE
Restores the database in the chosen HPMM or IOP. The
module must be in the Idle state (not valid for the secondary
HPMM). The command is executed by selecting the ENTER
target.
RESTORE ALL
Restores the database in the chosen HPMM and all IOPs.
The modules must be in the Idle state. The command is
executed by selecting the ENTER target.
SAVE ALL
Saves the database from the chosen HPMM and all IOPs
into either the History Module or removable media. This is
sometimes called “Checkpointing.” The command is
executed by selecting the ENTER target.
SIMULATOR LOAD
Loads the I/O Simulator personality and selected database
to the chosen HPMM. If the primary HPMM is chosen, the
database is also restored in all simulated IOPs that are in
the Idle state. The command is executed by selecting the
ENTER target.
CANCEL
Clears the PROGRAM LOAD, RESTORE MODULE,
RESTORE ALL, SAVE ALL, and ENTER command targets
from the display.
ENTER
Executes the LOAD/SAVE RESTORE function command.