2 Equipment Description
2.13 Field Termination Assembly
R688
HPM High-Performance Process Manager Service
79
December 2020
Honeywell
Vertical orientation
Standard and Galvanically Isolated FTAs are mounted on vertically oriented 3-foot long FTA Mounting
Channel segments; however, Standard and Galvanically Isolated FTAs must not be mounted on the same
FTA Mounting Channels.
Galvanically Isolated FTAs can be mounted on an FTA Mounting Channel that is above or below an
FTA Mounting Channel that has standard FTAs mounted on it, but the field wiring must never be routed
in the standard FTA’s channel.
Horizontal orientation
Optionally, Galvanically Isolated FTAs can be mounted on horizontally oriented 2-foot long FTA
Mounting Channels.
SHOCK HAZARD
Troubleshooting, opening this equipment and removing any panels or covers
will expose the
user
to the risk of a shock hazard. There are no
user
serviceable parts inside this equipment. Refer all servicing only to
qualified
service personnel
.