11 Servicing
SMGB0070 rev. 1 - 08/2011
296
No.
Part
1
Thermistor holder
2
Holder
3
Td Thermistor
4
Thermistor fixing plate
5
Rubber cap Th Thermistor
6
Compressor
No.
Part
1
Indication of terminal number
2
Terminal box cover
3
Compressor wires
No.
Part
1
Compressor wires (3 wires)
2
Fix it with screw
N O T E
• The compressor is connected by brazing. Check to ensure whether there are flammable things around or not
when using a burner for pipe connections. If you do not´, oil existing pipe inside may ignite.
• Do not expose the refrigerant cycle to the atmosphere for a long period in order to avoid water and foreign
particles entering into the refrigerant cycle. After removing the compressor, replace it quickly. If it is exposed
to the ambiance for a long period, seal both suction and discharge pipes.
• Remove the cap for the compressor just before replacing the compressor. Before assembling the compressor,
seal the suction pipe and discharge pipe with tape to protect the compressor interior from foreign particles.
Remove the tape when connecting the pipes.
• Match the terminal No. with the mark band No. when reassembling. If the wiring is connected incorrectly, the
compressor may be damaged due to reverse rotation.
• If there is a clearance between the oil heater and the compressor due to wire overlapping, excessive heat is
generated there. Then the oil heater is failed due to overheating. When mounting the reassembled oil heater,
this point should be taken into account.
• If the oil heater lead wire is caught on the spring, the lead wire may be cut due to vibration. When reassembling,
attention should be paid to the lead wire
.
C A U T I O N
All compressor pipes must be brazed to be connected to the refrigerant circuit. Ensure that all the sourrounding
is free of flammable objects and liquids when performing piping brazing work.
2
1
3
4
5
6
2
1
3
2
1
Details for compressor
terminals
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......