5 Control system
SMGB0070 rev. 1 - 08/2011
131
5
Fixed water temperature setting
OTC has no effect on this setting. The user will select a fixed water outlet temperature between 5ºC and 21ºC using the
user interface (LCD Controller).
TF
n
Outlet temperature set-point ºC
Outdoor ambient temperature (ºC)
Where:
TF
n
: Fixed water temperature setting.
n: heating circuit number (n= 1 or 2).
CODE
REF
Description
Default Value
Range
Steps
Units
CIRCUIT 1 (Direct circuit)
3-018
TF1
Fixed Tº C1
19
(3-020)~ (3019)
1
ºC
CIRCUIT 2 (Mixed circuit)
3-118
TF2
Fixed Tº C2
19
(3-120)~ (3119)
1
ºC
N O T E S
• Default values are same for both circuits in order to prevent low temperature in the Refreshing floor circuit.
• Parameters (3-0(1)20)~(30(1)19) are defined by Maximum and minimum water outlet temperature selected by
installer (See bellow).
C A U T I O N
• It is the installer’s responsibility to make sure no unwanted situation occurs (for example: water temperature
setting too low into floor refreshing).
• Be aware that the water set-point for circuit 2 will always be higher than water calculation for circuit 1.
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......