5 Control system
SMGB0070 rev. 1 - 08/2011
139
5
•
Thermo OFF condition by room thermostat
If Room Temperature Roff is higher (heating operation) or lower (cooling operation) than Room Temperature set-point, it
must also be set to THERMO OFF (Compressor OFF, Heater OFF,…) and water pump must be turned OFF after over-run
time (if ECO Pump is selected).
-
Heating application:
If
Room Temperature > Room Set-point tempe Roff
à
Thermo OFF by Indoor temperature
If
Room Temperature < Room Set-point temperature
à
Thermo ON by Indoor temperature
N O T E
In case of multiple Room Thermostats: Thermo OFF occurs when all Thermostats are fulfilled.
-
Cooling application
If
Room Temperature < Room Set-point temperature - Roff
à
Thermo OFF by Indoor temperature
If
Room Temperature > Room Set-point temperature
à
Thermo ON by Indoor temperature
N O T E
In case of multiple Room Thermostats: Thermo OFF occurs when all Thermostats are fulfilled.
CODE
REF
Description
Default Value
Range
Steps
Units
3-032
Roff
Room Thermo OFF
3
0~5
1
ºC
•
Unit OFF status by room thermostat (Heating and cooling application)
If Room Temperature setting is 5ºC or 10ºC. (by pressing OFF button (5ºC) or Holidays button (10ºC) on User Thermostat),
the heating or cooling space selected will be turned OFF. When both User Thermostats are in question, the entire heating
or cooling space will be in the Unit OFF position.
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......