12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
347
12
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Decrease of
discharge gas
superheat
Refrigerant cycle is different from
the electrical system
Check refrigerant
cycle and the electrical
system
Repair wiring
Overcharged refrigerant
Measure pressure
Correctly charge refrigerant
Faulty Expansion Valve
Check expansion val
-
ve. Refer to
Checking
procedure for the elec-
tronic expansion valve
Replace expansion valve if
faulty.
Faulty PCB
Fault
Replace PCB and
check operation
Replace PCB if faulty
Disconnected
wires for expan-
sion valve control
Check connections
Repair wiring connections
Faulty
discharge
gas
thermistor
Fault
Measure resistance
Replace thermistor if faulty
Incorrect
mounting
Check mounting state
See
Alarm Code 08
Correctly mount thermistor
Incorrect
connection
Check connections
Remove looseness,
replace connector or repair
connections.
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......