6 LCD user’s interface
SMGB0070 rev. 1 - 08/2011
185
6
6.5
Unit configuration
The following chapters explain all the items contained on the Unit configuration for the user.
N O T E
Menus may be modified during configuration. Configuration will hide or display available options. For example,
if Circuit 2 is disabled, all circuit 2 options will be hidden.
6.5.1 Operation display
This is the list of operation display parameters that can be consulted. All of them are read-only. Most of these variables are
the same ones that can be consulted by 7-segment, taking information from the outdoor unit.
CODE
Description
Default Value
Range
Steps
Units
System Operation
1-000
Operation Status
OFF
OFF
Cool D-OFF
Cool T-OFF
Cool ON
Heat D-OFF
Heat T-OFF
Heat ON
DHW OFF
DHW ON
SWP OFF
SWP ON
Alarm XXX (XXX= Code number)
-
-
Unit Status
1-003
Indoor Exp. valve opening (%)
-
Variable value
-
%
1-103
Outdoor Exp. valve opening (%)
-
Variable value
-
%
1-004
Inverter Operation frequency (Hz)
-
Variable value
-
Hz
1-005
Defrosting
-
Variable value
-
-
1-006
Cause of stoppage
-
Variable value
-
-
1-010
Compressor running current (A)
-
Variable value
-
A
1-011
PCB Firmware
-
Variable value
-
-
1-012
Product spec code
-
Variable value
-
-
1-013
Mixing valve position (%)
-
Variable value
-
%
Actual Temperature
1-014
Water Inlet Tº
-
Variable value
-
ºC
1-015
Water outlet Tº
-
Variable value
-
ºC
1-115
Water outlet Tº Boiler
-
Variable value
-
ºC
1-215
Water outlet Tº C2
-
Variable value
-
ºC
1-315
DHW Water Tº
-
Variable value
-
ºC
1-415
SWP Tº
-
Variable value
-
ºC
1-016
Gas Tº
-
Variable value
-
ºC
1-016
Liquid Tº
-
Variable value
-
ºC
1-017
Outdoor Ambient Tº
-
Variable value
-
ºC
1-117
Outdoor Ambient Average Tº
-
Variable value
-
ºC
1-217
2nd ambient Tº
-
Variable value
-
ºC
1-218
Summer Sw-Off average Tº
-
Variable value
-
ºC
1-018
Discharge Gas Tº
-
Variable value
-
ºC
1-019
Suction gas Tº
-
Variable value
-
ºC
1-020
Room Tº C1
-
Variable value
-
ºC
1-120
Room Tº C2
-
Variable value
-
ºC
Set Point
1-021
OTC Supply set point C1
-
Variable value
-
ºC
1-022
OTC Supply set point C2
-
Variable value
-
ºC
1-023
Water Tº Setting
-
Variable value
-
ºC
1-024
Room Tº Set point C1
-
Variable value
-
ºC
1-124
Room Tº Set point C2
-
Variable value
-
ºC
1-025
DHW Tº set point
-
Variable value
-
ºC
Alarm History
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......