12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
390
Alarm code
72
Thermostat Heater Alarm
•
The alarm code is displayed on the LCD User interface.
•
The alarm code is displayed on the seven segments of the indoor unit PCB.
•
This alarm code is displayed when electrical heater’s thermal protection is open (>75ºC).
Reset the thermal
protector by
pressing reset
button
Is the electri-
cal heater
thermostat (THe)
open?
Check the reset button on
the thermal protector. If
button is ON a pre-set (and
there is continuity between
terminals), but the Electrical
Heater continues OFF.
Yes
No
Check Electrical
Heater thermal
fuse
Yes
Has the
Thermal fuse
blown?
No
Have the
Electrical fuses
(EF1/2/3) blown?
Contact your local dealer
No
Yes
Contact your local dealer
Yes
Replace fuses
Alarm control procedure:
-
Switch OFF Outdoor and Indoor Units
-
Electrical Heater Disabled
-
Water pumps continue running up to water <55ºC.
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......