7 Optional functions
SMGB0070 rev. 1 - 08/2011
205
7
7.1.5
Tariff input (electrical tariff input)
This function can be used to block the heat pump.
It allows an external tariff switch device to switch off the heat pump during peak electricity demand period.
When the system is working in combination with Boiler, the boiler will be switched ON to provide the necessary heating.
7 9
Tariff device
Tariff-switching
device
L
CODE
Description
Default Value
Range
8-008
Tariff function enabled/disabled
Disabled
Disabled / Enabled
8-010
Tariff action (00~03)
00
00:Heat pump blocked when signal is closed.
01:Heat pump blocked when signal is open.
02:DHW blocked when signal is closed.
03:DHW blocked when signal is open.
8-009
Use boiler instead of heat pump
when TARIFF Mode is ON
Disabled
Disabled / Enabled
8-011
Use DHW Heater instead of heat
pump when TARIFF Mode is ON
Disabled
Disabled / Enabled
N O T E
• User boiler o DHW Heater instead heat pump when Tariff Mode ON (8-009 & 8011) only has effect when tariff
action selected is heat pump blocked (NC or NO) (00 or 01).
• 8-009 has priority instead 8-011.
• When tariff action ON is it shown in LCD and seven segments.
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......