5 Control system
SMGB0070 rev. 1 - 08/2011
140
Circuit water pumps
Main water pump for heating or cooling circuit application
• Pump configuration (Standard & Economy function)
Pump control can be set to standard or Economy mode. This configuration is set using DSW4 pin 5.
When pin is OFF, pump will be in standard operation and pump always be in operation when space heating or cooling is
enabled, but when space heating or cooling is disabled using the LCD user interface or Thermostat OFF (intelligent ther-
mostat only), pump must be switched OFF and only switched ON by Domestic Hot water request.
1
0
1
0
0
1
Space Heating/
Cooling status
Heat Demand
by Thermostat
Water Pump
Request
No request
Enabled
Disabled
Run
Stop
Time
When pin is ON, pump will be in ECONOMY operation. Economy operation allows pump to stop when system is stopped
by demand OFF in room thermostat.
1
0
1
0
0
1
Heat Demand by
Thermostat
Space Heating/
Cooling status
Water Pump
No request
Request
Enabled
Disabled
Stop
Time
Run
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......