12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
387
12
Alarm code
EE
Compressor protection
This alarm code is displayed when one of the following alarms occurs three times within six hours. If the outdoor unit ope-
rates continuously without removing the cause of the alarm, the compressor may be seriously damaged.
Alarm code
Content of abnormality
02
Tripping of protection device in outdoor unit
07
Decrease in discharge gas superheat
08
Increase in discharge gas temperature
41
Cooling overload
42
Heating overload
47
Low pressure decrease protection activating
N O T E
You can check these alarms using the check mode 1. Follow the action that is indicated in each alarm chart. You
can clear these alarms only by turning OFF the main switch to the system. However, you must pay careful atten
-
tion before starting, because there is a possibility of causing serious damages to the compressors.
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......