12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
366
Alarm code
35
Incorrect indoor number setting
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
•
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit
number and the alarm code are displayed on the display of the outdoor unit PCB.
-
This alarm code is indicated 3 minutes after power is supplied to the outdoor unit when the indoor unit no. con-
nected to the outdoor unit is duplicated by setting of RSW.
N O T E S
• In case of H-LINK system, this alarm code is indicated when the refrigerant system setting on the outdoor unit
PCB and the indoor unit PCB are incorrectly set.
• In this case, set correctly refering to the section
Setting of DIP switches and RSW switches
after turning OFF
main switch.