12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
381
12
Alarm code
53
Transistor module protection activation (RAS-2HVRN2)
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
•
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit
number and the alarm code are displayed on the display of the outdoor unit PCB.
-
This alarm is displayed when the inverter PCB or DIP-IPM module detects the abnormal operation 7 times or
more than 7 times in 30 minutes. The retry operation is performed six times.
Conditions:
The abnormal current to the inverter PCB or DIP-IPM, such as short-circuited, grounded, overcurrent or control voltage
decrease.
Check the compressor.
(If there is a short-circuit
between phase lines or groun-
ded from any phase, replace
the compressor.)
No
Turn off power of inverter components,
disconnect U, V, W from compressor
terminals. Turn ON pin 1 of DSW1 on PCB1.
Does it trip? *2)
Is the heat exchanger of outdoor
unit clogged?
Remove clogging.
Replace the electrical box
Yes
Yes
No
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......