5 Control system
SMGB0070 rev. 1 - 08/2011
147
5
Target temperature
•
Space heating
Being a parallel system (either Heat Pump or Boiler), water setting will be the same as the water set-point for Heat pump
without outdoor unit temperature restrictions but with restrictions of Maximum water temperature by installer.
•
DHW heating
Water set-point for DHW is defined to 80 ºC.
•
Conditions for enabling and disabling boiler.
-
Conditions for Enabling
Unit will enable boiler operation if all the following conditions are met.
1
Heating operation selected (Space Heating or DHW)
2
Boiler or Heater complementary heating selected
3
Ambient temperature < Boiler Bivalent point (6-007) (-5ºC Default) more than (Waiting time for boiler) (6-006)
4
Water temperature (Two3) ≤ Water Temperature target (Ttwo) - Supply set point control offset (4ºC default) (6-001)
-
Conditions for Disabling
Unit will not enable boiler operation in any of the following conditions are met:
1
Demand OFF by Room Thermostat
2
Ambient temperature > Boiler Bivalent point (6-007) more than 10 minutes.
User variables:
CODE
REF
Description
Default Value
Range
Steps
Units
6-001
kscob
Supply set-point control offset
4.0ºC
0 ~10
1
ºC
6-006
WTBO
Waiting time for boiler
30 min
1 ~90
1
min
•
Conditions for THERMO ON/OFF Boiler:
-
Conditions for Thermo ON Enabling:
1
Water temperature (Two3) < Water temperature setting (Ttwo) - Supply set point offset (4ºC Default)
2
Room thermostat in demand ON.
-
Conditions for Thermo OFF:
When any of Conditions a, b, or c are fulfilled.
a.
Measured outlet temp value (Two3) ≥ Water temperature 5ºC.
b.
Outlet water temp (Two3) = Max water range temp by installer (1&2 (3-(0)(1)11)) + 2ºC.
c.
Thermo OFF by Room Thermostat.
N O T E
Complementary disabling functions for the boiler itself:
In any of the following conditions step will be forced to 0 (boiler off):
• Boiler is disabled by user or thermo OFF by itselfs
• There is an alarm related to boiler
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......