6 LCD user’s interface
SMGB0070 rev. 1 - 08/2011
197
6
DHW Timer
DHW Timer is the same as that displayed in user mode.
Anti-legionella
The user can only activate or de-activate it, while the Installer will have access to all configuration parameters.
CODE
REF
Description
Default Value
Range
Steps
Units
8-003
OpInt
Operation Day
Sunday
Daily / Mon ~ Sun
-
Day
8-005
StTim
Starting Time
01:00
(00~24)
-
Time
8-006
DHWSP
DHW Tº Set Point
70
50~70
-
ºC
8-007
KeepP
Duration (min)
10
10~60
-
Min
If function is turned ON (Status), it will start at selected time (Start Time) and on the selected day (Operation Interval) at the
selected temperature (Anti-legionella Set Point) for the selected amount of time (Interval Time).
C A U T I O N
Anti-legionella function is hidden by default. The Installer can choose to reveal it.
Swimming pool
This view is the same as that displayed in user mode.
Complementary heating
It will display the same parameters, with the addition of the those listed below.
CODE
REF
Description
Default Value
Range
Steps
Units
electrical Heater Configuration
5-006
MOT
Bivalent Point for EH
0
-20~20
1
ºC
5-001
ksco
Supply Set Point Offset
4
0 ~10
1
K
5-002
PB
Proportional Band (ºC/100%)
6.0
0~20
0.2
ºC/100%
5-003
IRF
Reset Factor (%/ºCmin)
2.5
0~20
0.1
%/ºC Min
5-004
ISWT
Inter-Stage Waiting Time (min)
5
0~10
1
Min
5-005
WTEH
Waiting Time for EH (min)
30
1~90
1
Min
Boiler Configuration
6-007
BB
Bivalent Point for Boiler
-5
-20~20
1
ºC
6-004
Bon
Minimum ON Time (min)
2
1~30
1
Min
6-005
Boff
Minimum OFF Time (min)
5
1~30
1
Min
6-006
WTBO
Waiting Time (min)
30
1~90
1
Min
6-001
Kscob
Boiler Offset Tº
4
0~10
1
ºC
6-009
BWTt
Waiting Time for DHW (min)
45
0~120
5
ºC
Solar Configuration
10-001
Sprior
Status
Disabled
Disabled
Enabled
-
-
3-126
T
DHWMSOL
DHW SOLAR Max Time (min)
60
30~240
1
Min
N O T E
In the case of the H Boiler configuration (5-000), BB (6-007) will have a range of –20~20 and the contro
-
ller must ensure that: BB (6-007) < 5ºC + MOT (5-006).
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......