12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
398
Alarm code
80
H-Link communication failure between Indoor and LCD User interface
•
The alarm code is displayed on the LCD User interface.
•
The alarm code is displayed on the seven segments of the indoor unit PCB.
•
This alarm code is displayed when there is no communication for 3 minutes between Indoor PCB1 and LCD User
interface.
Are the
connections between
PCB1 and LCD User
interface correctly
connected?
LCD
CN1-1
CN1-2
CN1-3
CN1-4
CN1-5
CN1-6
TB
TB2-1
TB2-2
TB2-3
TB2-4
PCB1
CN1-2
CN1-3
CN15-1
CN15-2
Yes
Wiring check, repair breaking of wire,
wrong wiring
No
Set the same address
Faulty LCD or PCB1
(Check it)
Yes
Contact your local dealer
Is the same
indoor outdoor
address between PCB1
(indoor unit) and LCD
User interface?
No
Alarm control procedure:
-
Switch OFF Outdoor and Indoor Units.
12.1.3
Troubleshooting in check mode
Refer to chapter
6 User interface.
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......