5 Control system
SMGB0070 rev. 1 - 08/2011
135
5
•
Minimum on time and ON/OFF time cycle
In order to reduce Thermo ON/OFF Cycles per hour, there are two additional functions for ON/OFF Thermostat.
These two functions are:
a.
Minimum ON Time: When Thermostat is demanded, a minimum ON time will be applied (including when demand
is OFF)
b.
Minimum OFF Time: When Thermostat is demanded, a minimum OFF time will be applied.
CODE
REF
Description
Default Value
Range
Steps
Units
3-030
Ron
Minimum ON Time
6
0~15
1
min
3-031
Roff
Minimum OFF Time
6
0~15
1
min
Request
Thermostat demand (by
ON/OFF Thermostat)
Unit Thermo ON/OFF
1
0
1
0
3-030
3-031
No request
No operation
Operation
Time