5 Control system
SMGB0070 rev. 1 - 08/2011
125
5
Second water temperature control
The mixing valve is controlled to maintain the second heating supply temperature at the second heating temperature
set-point. The mixing valve position is calculated with a proportional integral action (P+I) control algorithm based on the
difference between the heating supply set-point and the heating supply temperature.
Zone 2: Low temperature (30~35 ºC)
Zone 1
system
Hydraulic
Separator
Second temperature
control
Secondary
water pump
Motorized
3way valve
To YUTAKI S system
To YUTAKI S
system control
The system control then decides how much to open or close the mixing valve to achieve the desired position for the valve.
CODE
REF
Description
Default Value
Range
Steps
Units
3-133
PB
Proportional band of mixing valve
6.0K
-0.2~20
0.2
ºC
3-134
IRF
Integral reset factor of mixing valve
2.5
0.0~20
0.1
%
3-135
RTV
Running time factor of mixing valve
140
10~500
10
sec
N O T E
Heating and cooling operation have same values.
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......