12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
368
Alarm code
38
Abnormality of protective circuit for protection (outdoor unit) (RAS-(3-10)H(V)RNME-AF)
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
•
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit
number and the alarm code are displayed on the display of the outdoor unit PCB.
-
This alarm code is indicated when AC 220V or 240V is supplied to voltage PCN9#1 and #3 on PCB1 in the
outdoor unit during CMC is opened.
Is 220VAC or 240VAC
applied PCN9#1 and #3
during stoppage?
Faulty PCB1
No
Check wiring
connection except
PCB1
Yes, PCB is normal
N14
CN15
PCN10 PCN13
PCN8
PCN9
SEG1
Y52C
Y20A
Y21
YCH
DSW1
PSW1
PSW2
PSW3
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Faulty PCB1
Check PCB1 by
seft-checking
Replace PCB1
Summary of Contents for RWM-(H)FSN3E
Page 2: ......
Page 4: ......
Page 10: ......
Page 20: ......
Page 64: ......
Page 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Page 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Page 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Page 188: ......
Page 210: ......
Page 224: ......
Page 230: ......
Page 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Page 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Page 336: ......
Page 423: ......