Calibration
144
A4500-1.1
HBM: public
WTX120
Function/Secondary selection
Key
Menu
LC-Capacity
1000
Enter the nominal load of a load cell
in the unit selected in group 1 (Scale Parame
ters\Unit)
No.Of Lcs
3
Enter the number of connected load cells: max. 8
mV/V of LC1
1.99995
Enter the sensitivity of the first load cell.
Continue with the next load cell; after the last
load cell, continue with the next step.
Load(mV/V):
1.40000
Display the standardized signal for the maximum
load (20% dead load + 50% net load)
Information
The Clr key can be used to clear the value and enter a new one.