WA • Functions description and parameters list
If set to
0
the Powerloss function is disabled. The Undervoltage alarm is generated in the event of a power
failure.
If set to
1
the Powerloss function is enabled. In case of a power failure the function is enabled to try to control
the motor speed and prevent the intervention of the
Undervoltage
alarm.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.7.2 3402 Powerloss accel time
s
FLOAT
10.0 0.01 100.0
ERW
F__
Setting of the acceleration time used in the Powerloss operating mode. The acceleration ramp time is used
when
Powerloss mode = Restart
has been selected and must be adjusted to suit machine requirements.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.7.3 3404 Powerloss decel time
s
FLOAT
2.0
0.01
100.0
ERW F__
Setting of the deceleration time used during Powerloss operating mode.
The deceleration ramp time must be short enough (in case of low speeds) to allow the drive to enter regen-
eration mode quickly, otherwise the
Undervoltage
alarm is generated. If the deceleration ramp time setting is
too short, when the drive enters regeneration mode it might not be able to control the DC link voltage and the
Overvoltage
alarm would be generated.
Longer deceleration times are necessary at high motor speeds to prevent the
Overvoltage
alarm from being
generated.
This parameter must be adjusted so as to reach a compromise between low speed and high speed motor
operation.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.7.4 3410 Powerloss Vdcref
V
FLOAT
CALCF
0.0
CALCF
ERWZS FV_
Setting of the voltage control limit on the DC-link during a controlled stop with loss of supply voltage The
maximum value that can be set is the drive overvoltage limit.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.7.5 3420 Powerloss P gain
A/V FLOAT
CALCF
0
100000
ERWS F__
Setting of the proportional gain during the Powerloss function.
Increase in case of
Overvoltage
error; the
Undervoltage
alarm can also be prevented by increasing the
deceleration time.
Increase if the DC link voltage is set to a value other than the setpoint.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.7.6 3422 Powerloss I gain
ms FLOAT
CALCF
1.0
1000.0
ERWS F__
Setting of the integral gain during the Powerloss function.
Reduce if the DC link voltage is set to a value other than the setpoint.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.7.7 3438 Powerloss mode
ENUM
Ramp down
0
1
ERWZ F__
This parameter is used to configure the behaviour of the Powerloss function when the mains supply is re-
stored.
It is possible to set whether the drive should continue at zero speed or return to the setpoint when the mains
supply is restored. The drive does not automatically recognise the fact that the mains supply has been re-
stored. This information must be supplied from the outside via the
Powerloss mains src
digital input.
0
Ramp down
1
Restart
Summary of Contents for ADV200 WA
Page 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Page 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Page 275: ...ADV200 WA Block Diagrams 275 References ...
Page 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Page 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Page 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Page 279: ...ADV200 WA Block Diagrams 279 ...
Page 280: ...280 ADV200 WA Block Diagrams Commands ...
Page 281: ...ADV200 WA Block Diagrams 281 ...
Page 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Page 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Page 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Page 285: ...ADV200 WA Block Diagrams 285 ...
Page 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Page 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Page 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Page 289: ...ADV200 WA Block Diagrams 289 Functions ...
Page 290: ...290 ADV200 WA Block Diagrams ...
Page 291: ...ADV200 WA Block Diagrams 291 ...
Page 292: ...292 ADV200 WA Block Diagrams ...
Page 293: ...ADV200 WA Block Diagrams 293 Process ...
Page 294: ...294 ADV200 WA Block Diagrams ...
Page 295: ...ADV200 WA Block Diagrams 295 ...
Page 296: ...296 ADV200 WA Block Diagrams ...
Page 297: ...ADV200 WA Block Diagrams 297 ...
Page 298: ...298 ADV200 WA Block Diagrams ...
Page 299: ......