130
ADV200
WA • Functions description and parameters list
0
Ignore
1
Warning
2
Disable
3
Stop
4
Fast stop
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.53 7702 Broken belt torque
perc
FLOAT
0.0 0.0 100.0
RW
VS
Setting of the percentage by which the torque must fall below the rated value for the alarm to be activated.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.54 7704 Broken belt delay
s
UINT16
30
1
3600
RW
VS
Setting of the delay after which the
Broken belt
alarm is activated. If the conditions causing this alarm return
to normal before the end of the set time, the alarm is not activated.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.55 7706 Broken belt spd thr
rpm INT16
100
0
CALCI
RW VS
Setting of the threshold value below which the alarm is not activated.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.56 7710 End curve activity
ENUM
Warning
0
4
RW VS
Setting of the behaviour of the drive if the
End curve
alarm is present. If the feedback measured (e.g. pres-
sure) stays below the reference value, with a programmable tolerance, for a programmable time and with the
pump at maximum speed, an end of curve alarm is generated. This may indicate a leak in the system.
0
Ignore
1
Warning
2
Disable
3
Stop
4
Fast stop
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.57 7712 End curve ref thr
perc
INT16
0 0 100
RW
VS
Setting of the speed threshold (as a percentage of
Full scale speed
(PAR 680, menu 5 REFERENCES)
which, if maintained with a feedback signal that is lower than the set value, the
End curve
alarm is generated.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.58 7714 End curve delay
s
UINT16
30
1
3600
RW
VS
Setting of the delay after which, if conditions remain unchanged, the
End curve
alarm is activated.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.59 7720 Dry pump activity
ENUM
Warning
0
4
RW VS
Setting of the behaviour of the drive if the
Dry pump
alarm is present. The
Dry pump
alarm is activated with
the
No flow
alarm if the power delivered is below the threshold calculated for the minimum power curve. The
motor must also be running at maximum speed. This is because if the pump is dry, there is no pressure in the
system and the PID will increase to maximum speed.
0
Ignore
1
Warning
2
Disable
3
Stop
4
Fast stop
Summary of Contents for ADV200 WA
Page 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Page 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Page 275: ...ADV200 WA Block Diagrams 275 References ...
Page 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Page 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Page 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Page 279: ...ADV200 WA Block Diagrams 279 ...
Page 280: ...280 ADV200 WA Block Diagrams Commands ...
Page 281: ...ADV200 WA Block Diagrams 281 ...
Page 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Page 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Page 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Page 285: ...ADV200 WA Block Diagrams 285 ...
Page 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Page 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Page 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Page 289: ...ADV200 WA Block Diagrams 289 Functions ...
Page 290: ...290 ADV200 WA Block Diagrams ...
Page 291: ...ADV200 WA Block Diagrams 291 ...
Page 292: ...292 ADV200 WA Block Diagrams ...
Page 293: ...ADV200 WA Block Diagrams 293 Process ...
Page 294: ...294 ADV200 WA Block Diagrams ...
Page 295: ...ADV200 WA Block Diagrams 295 ...
Page 296: ...296 ADV200 WA Block Diagrams ...
Page 297: ...ADV200 WA Block Diagrams 297 ...
Page 298: ...298 ADV200 WA Block Diagrams ...
Page 299: ......