ADV200 WA • Troubleshooting
267
E – TROUBLESHOOTING - Alarms
Note !
To reset alarms, see Quick start guide,
paragraph 6.6.1
.
In the following table, the Code is visible only from serial line.
Code
Error message shown on
the display
Sub-code
Description
0
No alarm
Condition:
No alarm present
1
Overvoltage
Condition: DC link overvoltage alarm due to energy recovered from the motor.
The voltage arriving at the drive power section is too high compared to the maximum threshold relating to
the PAR 560
Mains voltage
parameter setting.
Solution:
- Extend the deceleration ramp.
- Use a braking resistor between terminals BR1 and BR2 to dissipate the recovered energy
- Use the VDC Control function
2
Undervoltage
Condition:
DC link undervoltage alarm.
The voltage arriving at the drive power section is too low compared to the minimum threshold relating to
the PAR 560
Mains voltage
parameter setting due to:
- the mains voltage being too low or overextended voltage drops.
- poor cable connections (e.g. loose contactor terminals, inductance, filter, etc. ).
Solution:
Check the connections.
3
Ground fault
Condition:
Ground short circuit alarm
Solution:
- Check drive and motor wiring.
- Check that the motor is not grounded.
4
Overcurrent
Condition: Instantaneous overcurrent protection intervention alarm.
This may be due to the incorrect setting of current regulator parameters or a short circuit between phases
or ground fault on the drive output.
Solution:
- Check the current regulator parameters
- Check wiring towards the motor
5
Desaturation
Condition: Instantaneous overcurrent in the IGBT bridge alarm.
Solution:
Switch the drive off and then switch it on again.
If the alarm persists, contact the technical service centre.
6
MultiUndervolt
Condition:
The number of attempted automatic restarts after the
Undervoltage
alarm has exceeded the set
PAR 4650
UVRep attempts
value in the PAR 4652
UVRep delay
time.
Solution:
Too many Undervoltage alarms.
Adopt the proposed solutions for the Undervoltage alarm.
7
MultiOvercurr
Condition:
2 attempted automatic restarts after the Overcurrent alarm within 30 seconds. If more than 30
seconds pass after the Overcurrent alarm was generated, the attempt counter is reset.
Solution:
Too many Overcurrent alarms. Adopt the proposed solutions for the Overcurrent alarm.
8
MultiDesat
Condition:
2 attempted at automatic restarts after the Desaturation alarm within 30 seconds. If more than
30 seconds pass after the Desaturation alarm was generated, the attempt counter is reset.
Solution:
Too many
Desaturation
alarms.
Adopt the proposed solutions for the
Desaturation
alarm.
9
Heatsink OT
Condition:
Heatsink temperature too high alarm
Solution:
- Verify the correct operation of the cooling fan.
- Check that the heatsinks are not clogged
10
HeatsinkS OTUT
Condition:
Heatsink temperature too high or too low alarm
The temperature has exceeded the upper or lower limit set for the linear temperature transducer.
Solution:
- Verify the correct operation of the cooling fan.
- Check that the heatsinks are not clogged
- Check that the openings for the cabinet cooling air are not blocked.
11
Intakeair OT
Condition:
Intake air temperature too high alarm.
Solution:
Check correct fan operation
Summary of Contents for ADV200 WA
Page 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Page 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Page 275: ...ADV200 WA Block Diagrams 275 References ...
Page 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Page 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Page 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Page 279: ...ADV200 WA Block Diagrams 279 ...
Page 280: ...280 ADV200 WA Block Diagrams Commands ...
Page 281: ...ADV200 WA Block Diagrams 281 ...
Page 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Page 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Page 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Page 285: ...ADV200 WA Block Diagrams 285 ...
Page 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Page 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Page 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Page 289: ...ADV200 WA Block Diagrams 289 Functions ...
Page 290: ...290 ADV200 WA Block Diagrams ...
Page 291: ...ADV200 WA Block Diagrams 291 ...
Page 292: ...292 ADV200 WA Block Diagrams ...
Page 293: ...ADV200 WA Block Diagrams 293 Process ...
Page 294: ...294 ADV200 WA Block Diagrams ...
Page 295: ...ADV200 WA Block Diagrams 295 ...
Page 296: ...296 ADV200 WA Block Diagrams ...
Page 297: ...ADV200 WA Block Diagrams 297 ...
Page 298: ...298 ADV200 WA Block Diagrams ...
Page 299: ......