176
ADV200
WA • Functions description and parameters list
Selection of the origin (source) of the digital signal that forces pump alternation with an external command.
The signal used for this function can be set from among those available in the “
L_DIGSEL4
” selection list.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.15 7128 Altern restart delay
s
UINT16
30
1
3600
RW
VS
Setting of the delay after stopping the master pump before re-starting. After the alternation event the master
pump is stopped and the follower pump relays are opened. This time must pass before restarting the pumps
to be sure that those not controlled by the drive have also stopped
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.16 7130 Pump 1 intlock src
LINK 16BIT
6000
0
16384
RW VS
26.14.17 7130 Pump 2 intlock src
LINK 16BIT
6000
0
16384
RW VS
26.14.18 7132 Pump 3 intlock src
LINK 16BIT
6000
0
16384
RW VS
26.14.19 7134 Pump 4 intlock src
LINK 16BIT
6000
0
16384
RW VS
26.14.20 7138 Pump 5 intlock src
LINK 16BIT
6000
0
16384
RW VS
26.14.21 7140 Pump 6 intlock src
LINK 16BIT
6000
0
16384
RW VS
26.14.22 7142 Pump 7 intlock src
LINK 16BIT
6000
0
16384
RW VS
26.14.23 7144 Pump 8 intlock src
LINK 16BIT
6000
0
16384
RW VS
Selection of the origin (source) of the digital signal that indicates the availability of pump X. The signal used
for this function can be set from among those available in the “
L_DIGSEL4
” selection list.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.24 7150 Pump 1 out mon
BIT
1 0 1 R
VS
26.14.25 7152 Pump 2 out mon
BIT
1 0 1 R
VS
26.14.26 7154 Pump 3 out mon
BIT
1 0 1 R
VS
26.14.27 7156 Pump 4 out mon
BIT
1 0 1 R
VS
26.14.28 7158 Pump 5 out mon
BIT
1 0 1 R
VS
26.14.29 7160 Pump 5 out mon
BIT
1 0 1 R
VS
26.14.30 7162 Pump 7 out mon
BIT
1 0 1 R
VS
26.14.31 7164 Pump 8 out mon
BIT
1 0 1 R
VS
The status of follower pump X is displayed. If this parameter is set to 1, the pump may be controlled. This
signal must be connected to the digital output that controls the fixed-speed pump X control relay.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.32 7170 Pump 1 lead mon
BIT
1 0 1 R
VS
26.14.33 7172 Pump 2 lead mon
BIT
1 0 1 R
VS
26.14.34 7174 Pump 3 lead mon
BIT
1 0 1 R
VS
26.14.35 7176 Pump 4 lead mon
BIT
1 0 1 R
VS
26.14.36 7178 Pump 5 lead mon
BIT
1 0 1 R
VS
26.14.37 7180 Pump 6 lead mon
BIT
1 0 1 R
VS
26.14.38 7182 Pump 7 lead mon
BIT
1 0 1 R
VS
26.14.39 7184 Pump 8 lead mon
BIT
1 0 1 R
VS
The status of master pump X is displayed. If this parameter is set to 1, the speed-controlled pump is connect-
ed and the output that controls the relay for connecting the pump directly to the supply mains is not allowed.
This signal must be connected to the digital output that controls the pump X control relay.
Summary of Contents for ADV200 WA
Page 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Page 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Page 275: ...ADV200 WA Block Diagrams 275 References ...
Page 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Page 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Page 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Page 279: ...ADV200 WA Block Diagrams 279 ...
Page 280: ...280 ADV200 WA Block Diagrams Commands ...
Page 281: ...ADV200 WA Block Diagrams 281 ...
Page 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Page 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Page 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Page 285: ...ADV200 WA Block Diagrams 285 ...
Page 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Page 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Page 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Page 289: ...ADV200 WA Block Diagrams 289 Functions ...
Page 290: ...290 ADV200 WA Block Diagrams ...
Page 291: ...ADV200 WA Block Diagrams 291 ...
Page 292: ...292 ADV200 WA Block Diagrams ...
Page 293: ...ADV200 WA Block Diagrams 293 Process ...
Page 294: ...294 ADV200 WA Block Diagrams ...
Page 295: ...ADV200 WA Block Diagrams 295 ...
Page 296: ...296 ADV200 WA Block Diagrams ...
Page 297: ...ADV200 WA Block Diagrams 297 ...
Page 298: ...298 ADV200 WA Block Diagrams ...
Page 299: ......