26.7 – PROCESS/FILL
The purpose of the filling function is to avoid water hammering when a system is filled too quickly.
Different methods must be used to fill the horizontal and vertical pipes: in horizontal pipes the pressure does not in-
crease during filling, whereas in vertical pipes it increases as the water level rises.
It is a good idea, when filling horizontal pipes, to maintain a constant rpm for a previously set time, whereas vertical
pipes should be filled according to a pressure ramp with previously defined slope to reach a set pressure. For mixed
pipes use a combination of the two methods.
Controlled filling is performed in two stages:
Stage 1 (horizontal pipes): The pump runs at
Fill speed
for
Fill speed time
. This stage cannot be performed if
Fill
speed time
= 0 (which is the default setting).
Stage 2 (vertical pipes): this stage is enabled after stage 1. The pressure reference is increased up to the value of
Fill
setpoint
in
Fill speed time
. When the reference applied reaches the setpoint, the system enters normal operating
mode with the PID controlling the main reference. This stage may be skipped by setting
Fill setpoint
= 0 (which is the
default setting) and moving directly to
normal PID
control.
The “Fill” function is performed each time the system is started.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.7.1 7470 Fill enable
ENUM
Disable 0
1
RW
VS
Enabling of the fill function.
0
Disable
1
Enable
Set to 0 to disable the fill function.
Set to 1 to enable the fill function.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.7.2 7472 Fill speed
rpm
INT16
0 0 CALCI
RW
VS
Setting of the pump speed during horizontal pipe fill.
Summary of Contents for ADV200 WA
Page 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Page 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Page 275: ...ADV200 WA Block Diagrams 275 References ...
Page 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Page 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Page 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Page 279: ...ADV200 WA Block Diagrams 279 ...
Page 280: ...280 ADV200 WA Block Diagrams Commands ...
Page 281: ...ADV200 WA Block Diagrams 281 ...
Page 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Page 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Page 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Page 285: ...ADV200 WA Block Diagrams 285 ...
Page 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Page 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Page 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Page 289: ...ADV200 WA Block Diagrams 289 Functions ...
Page 290: ...290 ADV200 WA Block Diagrams ...
Page 291: ...ADV200 WA Block Diagrams 291 ...
Page 292: ...292 ADV200 WA Block Diagrams ...
Page 293: ...ADV200 WA Block Diagrams 293 Process ...
Page 294: ...294 ADV200 WA Block Diagrams ...
Page 295: ...ADV200 WA Block Diagrams 295 ...
Page 296: ...296 ADV200 WA Block Diagrams ...
Page 297: ...ADV200 WA Block Diagrams 297 ...
Page 298: ...298 ADV200 WA Block Diagrams ...
Page 299: ......