ADV200 WA • Functions description and parameters list
109
23 – COMMUNICATION
23.1 – COMMUNICATION/RS485
The ADV200 drive is provided with a standard port (9 pole sub-D connector: XS) for connecting the RS485 serial line used
for drive-PC point-to-point communication (via the GF-eXpress configuration software) or for the multidrop connection.
The RS485 serial line format is: 8 data bits, no parity and one stop bit.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
23.1.1 3800 Drive address
UINT16
1 1 255
ERW
VS
Setting of the address to which the drive responds when connected to the RS485 serial line.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
23.1.2 3802 Serial baudrate
ENUM
38400
0
2
ERW VS
Setting of the RS485 serial communication speed (Baud Rate).
0
9600
1
19200
2
38400
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
23.1.3 3810 Serial parameter
ENUM
None,8,1
0
3
ERW VS
Setting of the format of the RS485 serial communication data.
0
None,8,1
1
None,8,2
2
Even,8,1
3
Odd,8,1
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
23.1.4 3804 Serial protocol
ENUM
Modbus
0
1
ERW VS
Setting of the serial communication protocol:
0
Modbus
1
Jbus
Setting to
0
selects the Modbus RTU (Remote Terminal Unit) serial communication protocol.
Setting to
1
selects the Jbus serial communication protocol. The Jbus protocol is functionally identical to the
Modbus, except for the different numbering of addresses: in the Modbus these start from zero (0000 = 1st
address) while in the JBUS they start from one (0001 = 1st address) and maintain this difference throughout
numbering.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
23.1.5 3806 Serial delay
ms
UINT16
0 0 1000
ERW
VS
Setting of the minimum delay between the drive receiving the last byte and starting its response. This delay
avoids conflicts on the serial line when the RS485 interface that is used has not been pre-set for automatic
Tx/Rx switching. The parameter only concerns the use of the standard RS485 serial line.
Example: if the delay in Tx/Rx switching on the master is a maximum of 20ms, the Ser answer delay param-
eter must be set to at least 20ms: 22ms
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
23.1.6 3808 Serial swap data
BIT
0 0 1 ERW
VS
This parameter enables the exchange of the reading of the High and Low parts of the words for FLOAT,
UINT32, INT32 type parameters when using the Modbus protocol.
Summary of Contents for ADV200 WA
Page 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Page 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Page 275: ...ADV200 WA Block Diagrams 275 References ...
Page 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Page 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Page 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Page 279: ...ADV200 WA Block Diagrams 279 ...
Page 280: ...280 ADV200 WA Block Diagrams Commands ...
Page 281: ...ADV200 WA Block Diagrams 281 ...
Page 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Page 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Page 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Page 285: ...ADV200 WA Block Diagrams 285 ...
Page 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Page 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Page 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Page 289: ...ADV200 WA Block Diagrams 289 Functions ...
Page 290: ...290 ADV200 WA Block Diagrams ...
Page 291: ...ADV200 WA Block Diagrams 291 ...
Page 292: ...292 ADV200 WA Block Diagrams ...
Page 293: ...ADV200 WA Block Diagrams 293 Process ...
Page 294: ...294 ADV200 WA Block Diagrams ...
Page 295: ...ADV200 WA Block Diagrams 295 ...
Page 296: ...296 ADV200 WA Block Diagrams ...
Page 297: ...ADV200 WA Block Diagrams 297 ...
Page 298: ...298 ADV200 WA Block Diagrams ...
Page 299: ......