transient effect. This parameter must have a value that is greater than that set in parameter
7102 Staging
bandwidth
.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.6 7110 Override time
s
UINT16
30
1
3600
RW
VS
Setting of the duration of bandwidth override after switching.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.7 7112 Staging speed
perc INT16
30
0
100
RW VS
Setting of the speed of connection of a follower pump. To avoid jumps in pressure, during the connection of a
follower pump, the motor speed is changed by the value set in this parameter. The pump is connected when
this speed is reached.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.8 7114 Destaging speed
perc INT16
70
0
100
RW VS
Setting of the speed of disconnection of a follower pump. To avoid jumps in pressure, during the disconnec-
tion of a follower pump, the motor speed is changed by the value set in this parameter The pump is discon-
nected when this speed is reached.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.9 7116 Destage time
s
UINT16
0 1 3600
RW
VS
Setting of the time after which, if the speed-controlled pump is at minimum speed, and the feedback signal is
within the bandwidth, a pump is deactivated at the fixed speed. The purpose of this function is to prevent the
drive working too long in a limit zone where feedback cannot be controlled. This improves system efficiency.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.10 7118 Pumps cycle
BIT
0 0 1 RWZ
VS
Enabling of the pump cycle function. If this parameter is set to 1, the auxiliary pumps are activated in rotation
rather than following a constant order. The pump that has been used the least number of hours is activated
first and the one that has been used for the most hours is the first to be switched off. The hours of operation
are calculated from the last startup, thus if the drive is disconnected the sequence is re-initialised. This func-
tion only applies to fixed-speed follower pumps.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.11 7120 Alternation mode
ENUM
Disable 0
1
RWZ
VS
Enabling of speed-controlled pump alternating mode
0
Disable
1
Enable
Set to
0
to disable the master pump alternating function.
Set to
1
to enable the master pump alternating function.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.12 7122 Alternation time
min
UINT16
0 0 999
RW
VS
Setting of the alternating time interval. This parameter defines the maximum continuous operating time of the
speed-controlled pump.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.13 7124 Alt actual time
h.min
UINT16
1 0 9999999
RW
VS
The time since the last alternation of the speed-controlled pump is displayed.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.14.14 7126 Altern ext event src
LINK 16BIT
6000
0
16384
RW VS
Summary of Contents for ADV200 WA
Page 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Page 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Page 275: ...ADV200 WA Block Diagrams 275 References ...
Page 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Page 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Page 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Page 279: ...ADV200 WA Block Diagrams 279 ...
Page 280: ...280 ADV200 WA Block Diagrams Commands ...
Page 281: ...ADV200 WA Block Diagrams 281 ...
Page 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Page 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Page 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Page 285: ...ADV200 WA Block Diagrams 285 ...
Page 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Page 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Page 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Page 289: ...ADV200 WA Block Diagrams 289 Functions ...
Page 290: ...290 ADV200 WA Block Diagrams ...
Page 291: ...ADV200 WA Block Diagrams 291 ...
Page 292: ...292 ADV200 WA Block Diagrams ...
Page 293: ...ADV200 WA Block Diagrams 293 Process ...
Page 294: ...294 ADV200 WA Block Diagrams ...
Page 295: ...ADV200 WA Block Diagrams 295 ...
Page 296: ...296 ADV200 WA Block Diagrams ...
Page 297: ...ADV200 WA Block Diagrams 297 ...
Page 298: ...298 ADV200 WA Block Diagrams ...
Page 299: ......