GEK-105593C
57
PHASE A DIRECTIONAL TEST
•
Apply 4 times the pick up current at 0º on phase A. Positive is applied to terminal A1 and negative to
terminal A2.
•
Apply 60 V at 0º on phase C. Positive is applied to terminal A7 and negative to terminal A8.
•
Check that relay does not trip.
•
Gradually reduce the voltage to 4 V and check that relay still does not trip.
•
Reduce the voltage to 2.5 V and check that relay trips.
•
Apply 60 V at 180º on phase C.
•
Check that relay trips.
•
Apply 60 V at 320º on phase C.
•
Check that relay does not trip.
•
Apply 60 V at 130º on phase C.
•
Check that relay does not trip.
PHASE B DIRECTIONAL TEST
•
Apply 4 times the pick up current at 0º on phase B. Positive is applied to terminal B1 and negative to
terminal B2.
•
Apply 60 V with 0º on phase A. Positive is applied to terminal A5 and negative to terminal A6.
•
Check that relay does not trip.
•
Gradually reduce the voltage to 4 V and check that relay still does not trip.
•
Reduce the voltage to 2.5 V and check that relay trips.
•
Apply 60 V at 180º on phase A.
•
Check that relay trips.
•
Apply 60 V at 320º on phase A.
•
Check that relay does not trip.
•
Apply 60 V at 130º on phase A.
•
Check that relay does not trip.
PHASE C DIRECTIONAL TEST
•
Apply 4 times the pick up current at 0º on phase C. Positive is applied to terminal A3 and negative to
terminal A4.
•
Apply 60 V at 0º on phase B. Positive is applied to terminal B5 and negative to terminal B6.
•
Check that relay does not trip.
•
Gradually reduce the voltage to 4 V and check that relay still does not trip.
•
Reduce the voltage to 2.5 V and check that relay trips.
•
Apply 60 V at 180º on phase B.
•
Check that relay trips.
•
Apply 60 V at 320º on phase B.
•
Check that relay does not trip.
•
Apply 60 V at 130º on phase B.
•
Check that relay does not trip.
6.19. GROUND DIRECTIONAL UNIT (67NL)
Instantaneous trips (50NL, low level) are forced to test the directionality of the relay.
4 points are tested:
One located clearly inside the no-tripping zone
One located clearly within the tripping zone.
Another no-trip located at 5º from the upper limit of the no-tripping zone.
Another no-trip located at 5º from the lower limit of the no-tripping zone.
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...