GE Power Management
SMOR_B 1000/7000 QUICK REFERENCE GUIDE
* M
ODEL
L
IST
SMOR
_
_
_
1
_
2
1
_
_
00B
DESCRIPTION
FAMILY
0
3xIph +
Ig (without voltage functions)
1
3xIph +
Ig + 3xV
4
3xIph +
Ig + 3xV (ungrounded system)
6
3xIph +
Ig + Ig2 + 3xV
7
3xIph +
Ig + 3xV +
Vo (dedicated)
COMMUNICATIONS INTERFACE
0
RS232
1
Plastic F.O. + RS232
2
Glass F.O. + RS232
3
RS232+RS485
RANGES
*
* Ranges (see table)
MMI LAGUAGE
M
Spanish
D
English
EXPANSION
0
Without expansion board
1
With expansion board
AUXILIARY VOLTAGE
A
48
Vdc
H
110 / 250
Vdc
* R
ANGES
MODELS
A
B
C
D
E
F
G
H
1/7
Phase
1-12
0.2-2.4
1-12
1-12
1-12
0.5-6
0.5-6
2-16
Ground
1-12
0.2-2.4
0.2-2.4
0.5-6
0.1-1.2
0.2-2.4
0.1-1.2
0.2-2.4
4
Phase
0.2-2.4
1-12
Ground
0.005-0.1
0.005-0.1
6
Phase
1-12
1-12
Ground
0.2-2.4
0.2-2.4
Ground 2
0.025-0.3
0.5-6
* INPUTS / OUTPUTS
- Without expansion board:
•
6 digital inputs (two groups of 3 inputs with one common in each group).
•
2 groups of 4 configurable outputs with one common in each group.
•
2 trip contacts.
•
2 close contacts.
•
1 alarm contact
- With expansion board:
•
12 digital inputs (4 groups of 3 inputs with one common in each group).
•
2 groups of 4 configurable outputs with one common in each group.
•
4 configurable outputs electrically isolated.
•
2 trip contacts.
•
2 close contacts.
•
1 alarm contact.
•
2 coil supervision circuits.
* C
OEFFICIENTS FOR INVERSE CURVES
−
=
1
α
M
K
TD
time
CURVE
K
α
Inverse
0.13
0.02
Very Inverse
16
1
Extremely Inverse
96
2
* D
EFAULT
LEDS
C
ONFIGURATION
(
STANDARD MODEL
)
LED
CONFIGURATION
NMEMONIC
MEMORY
MODE
1
Phase A Trip
φΑ
TRIP
YES
FIXED
2
Phase B Trip
φ
B TRIP
YES
FIXED
3
Phase C Trip
φ
C TRIP
YES
FIXED
4
Ground Trip
GRN TRIP
YES
FIXED
5
Function 51/67 Trip
51/67 TRIP
YES
FIXED
6
Function 50/67 Trip
50/67 TRIP
YES
FIXED
7
Function 46 PT Trip
46 TRIP
YES
FIXED
8
Voltage Functions Trip
27/59/59N TRIP
YES
FIXED
9
Frequency Functions Trip
81 TRIP
YES
FIXED
10
Recloser Out of Service
79 OUT OF SERVICE
NO
FIXED
11
Reclose in progress
79 IN PROGRESS
NO
FIXED
12
Recloser LockOut
79 LOCKOUT
NO
FIXED
13
52 Open
52 OPEN
NO
FIXED
14
Coil Supervision Alarm
COIL SUPERV.
NO
FIXED
15
Critical Alarm
CRITICAL ALARM
NO
FIXED
16
Remote Mode
REMOTE MODE
NO
BLINK.
* D
EFAULT
I
NPUTS
C
ONFIGURATION
(S
TANDARD
M
ODEL
)
INPUT
CONFIGURATION
CONTACT
COMMON
CC1
Breaker input 52/b
C9
D10
CC2
Recloser Block
D9
D10
CC3
Recloser
UnBlock
C10
D10
CC4
50 P Block
C11
D12
CC5
50 N Block
D11
D12
CC6
Recloser Inhibit
C12
D12
CC7
Reclose Initiate
E9
F10
CC8
Phase Directional Blocking
F9
F10
CC9
Ground Directional Blocking
E10
F10
CC10
Oscillography Trigger
E11
F12
CC11
Active Table Select 0
F11
F12
CC12
Active Table Select 1
E12
F12
* C
ONFIGURABLE
I
NPUTS
O
PTIONS
:
•
Recloser Block (L)
•
Recloser Block (P)
•
Recloser Unblock (P)
•
Reclose Initiate (P)
•
Reclose Inhibition (L)
•
Oscillography External Trigger (P)
•
PT Secondary MCB Tripping (L)
•
Fail To Open Pickup (P)
•
Active Table Select
0 (L)
•
Active Table Select 1 (L)
•
Open Command (P)
•
Close Command (P)
•
Phase Directional Blocking (L)
•
Ground Directional Blocking (L)
•
Phase Instantaneous Blocking (L)
•
Ground Instantaneous Blocking (L)
•
Phase Units Blocking (L)
•
Ground Units Blocking (L)
•
Voltage
Uniis Blocking (L)
•
81U/81O Units Blocking (L)
•
46 PT Unit Blocking (L)
•
General Blocking (L)
NOTE:
(L) indicates Level input.
(P)
indicates Pulse input.
* D
EFAULT
O
UTPUTS
C
ONFIGURATION
(
STANDARD MODEL
)
OUTPUT
CONFIGURATION
CONTACT
COMMON
S1
51/67 P Pick-Up
C4
C6
S2
51/67 N Pick-Up
D4
C6
S3
46 PT Trip
C5
C6
S4
81 Trip
D5
C6
S5
27 / 59 Trip
C7
D6
S6
Last Trip
D7
D6
S7
Reclose In Progress
C8
D6
S8
Recloser Out of Service
D8
D6
S9
51/67 P Trip
E1
F1
S10
50/67 P Trip
E2
F2
S11
51/67 N Trip
E3
F3
S12
50/67 N Trip
E4
F4
* C
ONFIGURABLE
O
UTPUTS
O
PTIONS
:
Program Initiates
81O Pickup
51
Phase A Trip
Trips not allowed
Settings Change
27P Pickup
51 Phase B Trip
I with 52 open
Write Counters
59P Pickup
51 Phase C Trip
52 maintenance Al.
Cnfg. Change
59NH Pickup
50H
Phase A Trip
Coil 1 Cont. Failure
External Trigger
59NL Pickup
50H Phase B Trip
Coil 1 DC
supply Fail.
Communic
. Trigger
50H Phase C Trip
Coil 2 Cont. Failure
50L
Phase A Trip
Coil 2 DC supply Fail.
50L Phase B Trip
Closed Trip
Contacts
Reclose Command
51
Phase A Pickup
50L Phase C Trip
Active Table 1
79 Block Command.
51 Phase B Pickup
27P AB Trip
Active Table 2
79 Unblock Comma.
51 Phase C Pickup
27P BC Trip
Active Table 3
Open Command
50H
Phase A Pickup
27P CA Trip
Close Command
50H Phase B Pickup
59P AB Trip
50H Phase C Pickup
59P BC Trip
New Events
50L
Phase A Pickup
59P CA Trip
50L Phase B Pickup
52 Status
Activation Input 1
50L Phase C Pickup
79 Out of Service
Activation Input 2
27P AB Pickup
Reclose in progress
52
Failed to Open
Activation Input 3
27P BC Pickup
Reclose initiate
52
Failed to Close
Activation Input 4
27P CA Pickup
Ext.
Reclose Initiate.
Directional A
Activation Input 5
59P AB Pickup
Reclose Inhibit.
Directional B
Activation Input 6
59P BC Pickup
Directional C
59P CA Pickup
Last Trip
Directional N
79 Ready
Activation Input 7
51 PT Trip
Lockout: Fail to open
AND 1
Activation Input 8
51 NT Trip
Lockout:
Repet. Trip
AND 2
Activation Input 9
50
PH Trip
Lockout: No
cond.
AND 3
Activation Input 10
50 PL Trip
Lockout: Faulty 79
AND 4
Activation Input 11
50 NH Trip
Global Lockout
AND 5
Activation Input 12
50 NL Trip
AND 6
46 PT Trip
AND 7
81 U Trip
Recloser Block
AND 8
51PT Pickup
81 O Trip
AND 9
51NT Pickup
27 P Trip
Parallel E2PROM Al.
AND 10
50PH Pickup
59 P Trip
Serial E2PROM Al.
AND 11
50PL Pickup
59 NH Trip
In/Out of Service
AND 12
50NH Pickup
59 NL Trip
Default general
Sett.
AND 13
50NL Pickup
Default Table 1
Sett.
AND 14
46PT Pickup
Default Table 2
Sett.
AND 15
81U Pickup
Default Table 3
Sett.
AND 16
NOTE
: By using the INF key on the MMI you can see the status of the shadowed signals.
Measurements and communication estates are also available.
*
C
ONFIGURA
T
ION
S
ETTINGS
(7169)
SETTING
RANGE
DEFAULT
REMOTE PORT BAUD RATE
1200-115200
bauds
19200
bauds
REMOTE – STOP BITS
1-2
1
LOCAL PORT BAUD RATE
1200-19200
bauds
19200
bauds
LOCAL – STOP BITS
1-2
1
LOCAL SETTINGS
No Per/Per
Per
REMOTE SETTINGS
No Per/Per
Per
LOCAL OPERATIONS
No Per/Per
Per
REMOTE OPERATIONS
No Per/Per
Per
UNIT NUMBER
1 – 255
1
PASSWORD
0-99999
1
t TIMEOUT
0-86400
0
* SMOR_B S
OFTWARE
GE_INTRO
: Relay
Configuration .
GE_LOCAL
: Settings, Events,
Status.
GE_OSC
: Oscillography analysis.
* C
OMMUNICATIONS
SMOR_B
PC
DB 9
MODEM
3
2
3
2
3
2
1
4
4*
5
5
5
* Join 6 and 7 points too.
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...