GEK-105593C
56
•
Apply 1.5 times the pick up current and the relay should trip in 16 sec. Acceptable time range between
13.91 and 18.82 sec.
•
Apply 5 times the pick up current and the relay should trip in 2.03 sec. Acceptable time range between
1.88 and 2.13 sec.
EXTREMELY INVERSE CURVE
•
Set the relay as follows:
51NT Settings Group
Curve
EXTREMELY INVERSE
Time Dial
0.05
•
Apply 0.9 times the pick up current into phase C and the relay should not trip.
•
Apply 1.5 times the pick up current and the relay should trip in 3.87 sec. Acceptable time range between
3.24 and 4.65 sec.
•
Apply 5 times the pick up current and the relay should trip in 0.20 sec. Acceptable time range between
0.16 and 0.24 sec.
DEFINITE TIME
•
Set the relay as follows:
51PT Settings Group
Curve
DEFINITE TIME
Time Dial
1.0
•
Apply 0.9 times the pick up current into phase A and the relay should not trip.
•
Apply 1.1 times the pick up current and the relay should trip in 1 sec. Acceptable time range between
0.97 and 1.03 sec.
•
Apply 4 times the pick up current and the relay should trip in 1 sec. Acceptable time range between 0.97
and 1.03 sec.
6.18. PHASE DIRECTIONAL UNIT (67PL)
Instantaneous trips (50PL, low level) are forced to test the directionality of the relay.
4 points are tested:
•
One located clearly inside the no-tripping zone
•
One situated clearly within the tripping zone.
•
Another no-trip located at 5º from the upper limit of the no-tripping zone.
•
Another no-trip located at 5º from the lower limit of the no-tripping zone.
Enable only 50PL function and its related trip, and set its pick up and time delay to the minimum possible
•
Set the relay as follows:
Directionality Settings Group
51 PT Directional
NO
51NT Directional
NO
50PH Directional
NO
50PL Directional
YES
50NH Directional
NO
50NL Directional
NO
Phase Angle
45
Ground Angle
-45
V Loss Logic
Permission
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...