GEK-105593C
55
•
Apply 5 times the pick up current and the relay should trip in 2.03 sec. Acceptable time range between
1.88 and 2.13 sec.
EXTREMELY INVERSE CURVE
•
Set the relay as follows:
51PT Settings Group
Curve
EXTREMELY INVERSE
Time Dial
0.05
•
Apply 0.9 times the pick up current into phase C and the relay should not trip.
•
Apply 1.5 times the pick up current and the relay should trip in 3.87 sec. Acceptable time range between
3.24 and 4.65 sec.
•
Apply 5 times the pick up current and the relay should trip in 0.20 sec. Acceptable time range between
0.16 and 0.24 sec.
DEFINITE TIME
•
Set the relay as follows:
51PT Settings Group
Curve
DEFINITE TIME
Time Dial
1.0
•
Apply 0.9 times the pick up current into phase A and the relay should not trip.
•
Apply 1.1 times the pick up current and the relay should trip in 1 sec. Acceptable time range between
0.97 and 1.03 sec.
•
Apply 4 times the pick up current and the relay should trip in 1 sec. Acceptable time range between 0.97
and 1.03 sec.
6.17. GROUND TIME OVERCURRENT UNIT (51NT)
Enable only 51NT function and its related trip, and set the pick up to the minimum possible.
INVERSE CURVE
•
Set the relay as follows:
51NT Settings Group
Curve
INVERSE
Time Dial
1
•
Apply 0.9 times the pick up current into phase A and the relay should not trip.
•
Apply 1.5 times the pick up current and the relay should trip in 16 sec. Acceptable time range between
14.24 and 18.28 sec.
•
Apply 5 times the pick up current and the relay should trip in 4 sec. Acceptable time range between 3.87
and 4.10 sec.
VERY INVERSE CURVE
•
Set the relay as follows:
51NT Settings Group
Curve
VERY INVERSE
Time Dial
0.5
•
Apply 0.9 times the pick up current into phase B and the relay should not trip.
Summary of Contents for SMOR-B GEK 105593C
Page 5: ......
Page 9: ...GEK 105593C 4 ...
Page 25: ...GEK 105593C 20 FIGURE 5 RECLOSER STATES DIAGRAM 226B2200H1 SUMMARISED ...
Page 51: ...GEK 105593C 46 ...
Page 71: ...GEK 105593C 66 ...
Page 73: ...GEK 105593C 68 ...
Page 88: ...GEK 105593C 83 FIGURES FIGURES FIGURES FIGURES ...
Page 89: ...GEK 105593C 84 FIGURE 1 PANEL DRILLING DIMENSIONS FOR 19 RACK MODELS 226B6086H10 ...
Page 91: ...GEK 105593C 86 FIGURE 3 INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H1 ...
Page 92: ...GEK 105593C 87 FIGURE 4 VERY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H2 ...
Page 93: ...GEK 105593C 88 FIGURE 5 EXTREMELY INVERSE CHARACTERISTIC OPERATING CURVE 226B7414H3 ...
Page 94: ...GEK 105593C 89 FIGURE 6 RECLOSER PROGRAM FLOWCHART 226B2200H1 ...
Page 95: ...GEK 105593C 90 FIGURE 7 FRONT VIEW FOR 19 RACK MODELS 226B7412H9 ...
Page 96: ...GEK 105593C 91 FIGURE 8 FRONT VIEW FOR 1 2 RACK MODELS ...
Page 97: ...GEK 105593C 92 FIGURE 9 EXTERNAL CONNECTIONS FOR 19 MODELS 189C4101H1 ...
Page 100: ...GEK 105593C 95 FIGURE 13 REAR VIEW FOR 19 MODELS 226B7412H10 ...
Page 102: ...GEK 105593C 97 FIGURE 15 DIMENSIONS DIAGRAM FOR 19 MODELS 226B6086H10 ...